Abstract
The aim of this study is to evaluate the potential of thermal comfort enhancement in a selected
zone of a modern office building with high ratio of glazed façade and a heating / cooling
system with high thermal inertia, equipped with low-exergy radiant heating and cooling.
Experimental measurements performed over three reference weeks, distributed over heating,
transition and cooling period, revealed overheating during 15 % - 30 % of the evaluated time
intervals in the heating period. A simulation model of the reference zone with four variations
of ventilation and shading system control strategies was created in TRNSYS to investigate the
possibilities of thermal environment optimization. Three different heating/ cooling radiant
systems were implemented to the model with the optimal set-point variation. The simulations
indicate a potential to significantly enhance thermal comfort by improving the control strategy
of the heating system and of the external blinds, however, the difference between the thermal
environments created by the three different radiation systems were negligible.
URI
http://hdl.handle.net/20.500.11790/1568
Conference
Healthy Buildings 2017 Europe  
Subjects
Low-exergy radiant heating
thermal comfort
glazed façade
simulation program
optimization
Type
Konferenzbeitrag

 

FHB is participating in:

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Privacy policy
  • End User Agreement
  • Send Feedback