  5. Complex glass facade modelling for Model Predictive Control of thermal loads: impact of the solar load identification on the state-space model accuracy
 
  • Details

Complex glass facade modelling for Model Predictive Control of thermal loads: impact of the solar load identification on the state-space model accuracy

Publisher
Leykam
Source
Technologie- und Klimawandel: Energie-Gebäude-Umwelt, 473-481
Journal
Technologie- und Klimawandel : Energie – Gebäude – Umwelt  
Date Issued
2020-11-26
Author(s)
Veynandt, Francois  
Heschl, Christian  
Klanatsky, Peter  
Plank, Helmut  
Abstract
Above and beyond improving the efficiency of the building envelope and the energy supply
system, the demand-side flexibility in terms of load shifting and peak reduction are vital factors in further
increasing the share of volatile renewable energy sources. The thermal activation of building components,
like floors and ceilings, enables the cost-effective potential for short-term energy storage to fulfil these
requirements. In order to exploit the storage capabilities of active building systems, a reliable model predicted
control (MPC) approach is required. However, primarily if a large glass façade element is utilised,
the appropriate modelling of solar loads is critical for an effective MPC operation. Hence, based on a
dynamic building simulation tool, a characteristic map for the solar load prediction of a glass façade
system in combination of external venetian blinds was generated to enhance the state-space model approach
for the MPC algorithm. The comparison with a conventional state-space model approach shows
the integration of a detailed characteristic map can only marginally improve the prediction accuracy.
The additional information required from the glass façade manufacturer and the associated simulation
effort is not of substantial value. In contrast, the conventional grey box model enables an entirely datadriven
parameter identification, without the manufacturers’ data. Furthermore, the MPC optimisation
procedure, searching for the best control strategy, can be more efficient (solver-based optimisation), with
shorter computing turnaround times.
URI
http://hdl.handle.net/20.500.11790/1396
Funding(s)
PVadapt  
Type
Konferenzbeitrag
Product
Monitoring dataset from an office room in a real operating building, suitable for state-space energy modelling  
File(s)
Loading...
Thumbnail Image
Name

9783701104604_473.pdf

Size

2.85 MB

Format

Adobe PDF

Checksum

(MD5):4c216a4f8a19a71201b618af48d556f0

 

FHB is participating in:

Built with DSpace-CRIS software - Extension maintained and optimized by 4Science

  • Privacy policy
  • End User Agreement
  • Send Feedback